How often should you test and replace smoke and carbon monoxide alarms?

Updated November 12, 2026 · By The HomeMemory team

The short answer

CPSC says to test smoke and CO alarms every month and to change their batteries every year. USFA says to replace smoke alarms 10 years after the manufacture date, and CPSC says to replace any that are more than 10 years old. Kidde says CO alarms should be replaced every 7 to 10 years, depending on the model, and CPSC says to check the product literature.

How often, by task

TaskHow oftenWho says so
Test smoke alarmsOnce a monthUSFA, CPSC, First Alert Store
Test CO alarmsOnce a monthCPSC, First Alert Store
Change replaceable batteriesAt least once a yearUSFA, CPSC
Replace a smoke alarm10 years; USFA counts from the manufacture dateUSFA, CPSC, First Alert Store, Kidde (one Kidde page says 5 to 10 years)
Replace a CO alarm7 to 10 years, depending on the modelKidde; CPSC says to use the age in the product literature

The U.S. Fire Administration (USFA) says the whole smoke alarm should be replaced 10 years after the date it was made. CPSC says to replace smoke alarms that are more than 10 years old. The First Alert Store, a retailer site that calls itself the official online store for First Alert products, says that in most cases smoke alarms should be replaced after 10 years. Kidde's help center also says ten years for smoke alarms. One Kidde safety page puts it differently: it says smoke and combination alarms last 5 to 10 years from manufacture, depending on the model.

CO alarms are on a different clock. Kidde says its CO and combination smoke and CO alarms should be replaced every 7 to 10 years, depending on the model. CPSC does not give a single number. It says each CO alarm has a recommended replacement age, listed in the product literature or available from the maker.

Signs an alarm needs attention

The First Alert Store says a chirp at regular intervals often points to a weak battery, an end-of-life warning, or some other upkeep issue. Kidde says a low-battery smoke alarm chirps every 30 to 40 seconds, or every 60 seconds on some models, for at least seven days. On Kidde alarms with sealed batteries, a chirp every 30 seconds means the alarm itself is due for replacement.

Kidde says its CO alarms give an end-of-life warning every 30 seconds, and models with a screen show ERR or END. Kidde is clear that a CO alarm in end-of-life mode no longer senses carbon monoxide. It also says a new battery will not stop an end-of-life or sensor-error chirp. On another page, Kidde says a single chirp every 30 to 60 seconds often signals end of life, not only a low battery.

The First Alert Store lists other signs that an alarm should be replaced: it is 10 or more years old, it keeps chirping after you have worked through the troubleshooting steps, its case is yellowed, cracked or damaged, it gives recurring nuisance alarms, or its label is too worn to read the age. Kidde adds two more: the test button does not set off a loud alarm, or the alarm has been through heavy smoke or a fire.

Chirp and light patterns vary by model. The First Alert Store suggests finding the model number on the back of the alarm and checking that model's manual.

How to check and replace one

The First Alert Store describes the test this way. Press and hold the test button, listen for the loud test pattern, then let go and make sure the alarm goes quiet. CPSC notes a limit to this on CO alarms: the test button checks that the circuitry works, not how accurate the sensor is. Kidde makes a similar point: even if the test button works fine, the sensor inside may not be as effective.

For a hardwired smoke alarm, the First Alert Store gives these steps. It says to use a qualified electrician if the wiring is missing or damaged, or if you are unsure, and USFA says only qualified electricians should install hardwired smoke alarms.

  1. 01Shut off power to the alarm circuit at the breaker panel.
  2. 02Twist the old alarm off its mounting bracket.
  3. 03Unplug the wiring harness from the back of the old alarm.
  4. 04Fit the new mounting bracket to the electrical box if the new alarm needs it.
  5. 05Plug the wiring harness into the new alarm, using an adapter if the model calls for one.
  6. 06Put in the backup battery if the new alarm uses one.
  7. 07Twist the alarm onto its bracket and turn the breaker back on.
  8. 08Press the test button. If your alarms are interconnected, confirm the others sound too.

The First Alert Store recommends replacing a hardwired alarm with a compatible hardwired one when possible, especially on an interconnected system, and says not to burn or take apart old alarms.

How to find the manufacture date

The First Alert Store says the date is usually printed on a label on the back or side of the alarm, so you may need to take the unit off its bracket to read it. Kidde also points to the back of the alarm, or to the user guide. The First Alert Store says some CO alarms carry a replace-by date or a printed service-life note.

If the label is missing or unreadable, the First Alert Store says to treat the alarm as being of unknown age and replace it.

Sealed 10-year battery alarms

Some alarms run on a lithium battery that cannot be removed. USFA says that for these models you still test monthly, and when the time comes you replace the entire alarm following the manufacturer's instructions. CPSC says sealed lithium alarms can run for up to 10 years and that the whole unit is meant to be thrown out after that.

The First Alert Store says these units are built so the battery and the alarm reach the end of their service life at about the same point. USFA describes the battery in these models as nonreplaceable.

Where alarms go, and where they don't

For smoke alarms, USFA says to put one inside each bedroom, one outside each sleeping area, and at least one on every level, mounted on the ceiling or high on a wall. USFA recommends interconnected alarms, so that all of them sound when one does. CPSC says to keep smoke alarms away from kitchen appliances and fireplaces to cut down on false alarms, and to avoid spots near bathrooms, heating appliances, windows and ceiling fans.

For CO alarms, CPSC says to place one on each level of the home and outside sleeping areas. CPSC does not recommend putting them in kitchens or above fuel-burning appliances, and says to keep them away from heating vents and anywhere furniture or curtains could cover them. CPSC says plug-in and hardwired CO alarms should have a battery backup.

The sources differ on basements. CPSC says CO alarms should not go in attics or basements unless someone sleeps there. The First Alert Store says to install CO alarms on every level, basements included. CPSC says to install CO alarms according to the manufacturer's instructions, and notes that many states and local governments now require them, so check with your local building code official.

If a CO alarm goes off

CPSC says never to ignore a sounding CO alarm, and not to go looking for the source. Move outside to fresh air immediately. Then call your emergency services, the fire department or 911. After calling, do a head count to check that everyone is accounted for. Do not go back in until the emergency responders have given you permission. CPSC's reason is plain: you could lose consciousness and die if you go back into the home.

CPSC says the early signs of low to moderate CO poisoning feel like the flu without a fever: headache, tiredness, shortness of breath, nausea and dizziness. CPSC also notes that in rapidly developing, high-level exposures, such as from a generator used in a living space, people can quickly become confused and lose muscle control without first having milder symptoms, and will likely die if not rescued.

The schedule is the hard part

These tasks run on three different clocks: a monthly test, a yearly battery, and a replacement date measured in years that differs between smoke and CO alarms. CPSC says smoke alarms most often fail to sound because the battery is missing, dead or disconnected.

The manufacture date is printed on a label on the back or side of a device that sits on the ceiling or high on a wall, and Kidde says a CO alarm in end-of-life mode no longer senses carbon monoxide at all. That is the kind of thing a home should remember for you.

Common questions

Do alarms with a 10-year sealed battery ever need a new battery?

No. USFA says alarms with a nonreplaceable 10-year lithium battery are replaced as a whole unit, following the manufacturer's instructions. CPSC says the entire unit is meant to be disposed of after 10 years.

Why does my alarm keep chirping after I put in a new battery?

Kidde says an end-of-life or sensor-error warning will not respond to a battery change, so a chirp that keeps going after a fresh battery can mean the alarm has reached the end of its life. The First Alert Store also lists chirping that continues after troubleshooting as a sign to replace the unit.

If the test button works, is the alarm fine?

Not necessarily. CPSC says the test button on a CO alarm checks the alarm's circuitry, not the accuracy of its sensor. Kidde says the sensor may not be as effective even when the test button works fine.

When is a good time to change the batteries?

CPSC suggests changing smoke alarm batteries in the spring or fall, when you reset your clocks, and says to do it at least once a year.

Sources

This guide is general information. Your owner’s manual is the authority for your model, and gas appliances should be serviced by someone qualified to work on them.